7
|
4
|
Pool maintenance: pool walls and floor kept clean, free of debris and in good repair |
No |
No
|
No |
.2537(14) Keep pool surface and pool floor free of debris. Observed debris in pool. Clean. |
|
8
|
4
|
Pool maintenance: surface skimmers (with weirs, baskets and covers) or gutters clean, in good repair, and functioning properly, no floating debris |
No |
No
|
No |
.2518(k) Replace missing or damaged skimmer basket. Observed one damaged skimmer basket and one missing. They were replaced during inspection.
.2518(k) Keep skimmers free of debris so skimmers are capable of operating per manufacturer instruction. Observed large amount of debris in skimmer baskets. Removed during inspection. |
|
11
|
2
|
Pool maintenance: diving equipment, ladders, steps and handrails properly placed, in good repair |
No |
No
|
No |
.2521(a) Steps or ladders shall be provided every 75 ft along the shallow area perimeter. Ladder has been removed from one side of the shallow end of the pool. This creates a distance greater than 75 ft between steps and next ladder. Re-install. |
|
15
|
6
|
Premises: body hook and ring buoy with throw rope or lifeguard with rescue tube provided and properly located |
No |
No
|
No |
.2530(a) Provide ring buoy for rope 1.5 times the width of the pool or 50 ft whichever is less. Observed ring. Buoy rope greater than 50 ft. It was cut to 50 ft during inspection. |
|
24
|
4
|
Equipment room: approved pump, filter, and flow meter operating properly |
No |
No
|
No |
.2518(g) Keep flow meter operational. Flow meter was not operating properly. Repaired during inspection. |
|
25
|
2
|
Equipment room: equipment and chemicals kept in a dry, well-ventilated enclosure |
No |
No
|
No |
.2533(a) Pump room shall be weatherproof with a minimum ceiling height of 7 ft. Pump room has a chain link gate and screened windows - it is not weatherproof.
.2533(b) Provide sufficient lighting in pump room. Light bulb was missing in pump room. |
|
30
|
2
|
Dressing and sanitary facilities: approved water source, no cross connections |
No |
No
|
No |
Observed no backflow preventers at hose bibb on deck and one near restrooms. Provide. |