1
|
6
|
Water quality: water clear enough to clearly see bottom of pool and pool drain |
No |
No
|
No |
Skimmer equalizer covers in deep end covered in debris, unable to see clearly.
.2535(2) Main drains must be clearly visible from the pool deck. Operator cleaned and corrected. |
|
5
|
4
|
Water quality: daily written records of water quality and test kit kept on site |
No |
No
|
No |
Cyanuric acid had a "check" instead of reading at time of inspection.
.2535(11) Provide record keeping including daily records of disinfectant residual, pH, drain cover/grate inspections, pool water maintenance, and temperature, if applicable. Provide weekly recordings for cyanuric acid and total alkalinity weekly. Operator recorded reading as number. Corrected. |
|
11
|
2
|
Pool maintenance: diving equipment, ladders, steps and handrails properly placed, in good repair |
No |
No
|
No |
Ladder bolt at deep end coming out of second step.
.2521 Install ladders per manufacturer instructions. Operator repaired and corrected. |
|
17
|
4
|
Premises: decks unobstructed, properly drained, free of trip hazards |
No |
No
|
No |
Holes in deck greater than 1/2" at time of visit. Operator filled holes and corrected.
.2537(2) Decks shall be kept free of trip hazards or offsets greater than 1/2" due to deterioration or changes from original deck profile..2522(a) Provide 8 ft of clear walking space around the pool at all times (>1600 sq. ft).
Decking cracking at joints causing some offsets greater than 1/2" within 8' of pool. Severity at this time does not warrant permit action. Pool built in 1962. Advised repairs must be made before permitting for 2021 to eliminate offsets. Some visible repairs had been made at time of inspection. |
|
25
|
2
|
Equipment room: equipment and chemicals kept in a dry, well-ventilated enclosure |
No |
No
|
No |
Standing water in outdoor equipment area by filters. Pool built 1962. Backflow preventer removed from hose bibb. Operator replaced. Chemicals in pump room. .2533(d) Pump room floor shall be kept dry and free of standing water.
.2533(g) Provide a hose bib with backflow prevention device within 50 ft. of the equipment room.
.2534(2) Pools constructed after April 1, 2004 shall provide a separate room for chemical storage meeting Rule.2534. |
|
29
|
2
|
Dressing and sanitary facilities: required fixtures provided, clean, and in good repair |
No |
No
|
No |
Hot water over 110 degrees F in women's restroom at time of inspection. |