6
|
6
|
Submerged suction outlets meet ASME/ANSI A112.19.8-2007. Single drains protected. (.2537, .2539) GPM= ____Field verification complete=____ |
No |
No
|
No |
.2539(c) All pools, prior to permit issuance, shall provide documentation to the Department to verify suction outlet safety compliance. Observed flow meter reading >170RPM after backwash. CDI-VSP RPM lowered flow meter reading 150 GPM. Make
sure flow meter reading does not exceed 170GPM. |
|
16
|
4
|
Premises: fence or barrier with self-closing, self-latching gates properly constructed and maintained |
No |
No
|
No |
.2528(a) Pool fence shall be at least 48" in height measured from outside of barrier. Observed foothold (metal bar attached to main gate) 28” above ground. CDI-signs attached to gate over sign. Keep sign in place |
|
29
|
2
|
Dressing and sanitary facilities: required fixtures provided, clean, and in good repair |
No |
No
|
No |
.2526(k) Provide shatterproof mirrors. Observed mirrors not shatterproof |
|
30
|
2
|
Dressing and sanitary facilities: approved water source, no cross connections |
No |
No
|
No |
.2512(b) Water introduced into the pool, either directly or by the circulation system, shall be supplied through an air gap, anti-siphon vacuum breaker, or backflow preventer. Observed no backflow preventer on hose bib on pool deck |