Premises: decks unobstructed, properly drained, free of trip hazards |
No |
No
|
No |
Observed some deck cracks and offset in concrete near pool corner closest to pool entrance gate. ** Maintain deck in good repair. See .2537 MAINTENANCE (b)(2) |
|
25
|
2
|
Equipment room: equipment and chemicals kept in a dry, well-ventilated enclosure |
No |
No
|
No |
-- No natural cross draft ventilation or forced air ventilation in equipment/ chemical room building. ** Provide.
-- No light fixture in equipment/ chemical room building.
** Provide.
Note: CPO reports that a tree fell and severely damaged the pool equipment/chemical room building. (Pool circulation system remained intact). Pool circulation system/ equipment & chemical storage is in a stand alone building. EHS observed what essentially appears to be a new building - new walls, new roof & new door. EHS requested that CPO inform homeowners association that if building permits were not obtained for the re-construction of the pool equipment/ chemical room building, then a representative with the homeowners association needs to contact Mecklenburg County Commercial Technical Assistance Center @ (980) 314-2633 to determine if permits were in fact needed. The structure's lack of ventilation and absence of a light fixture do not meet the NC pool rules requirements and may also be in violation of the NC building code too. In addition, if the fire marshal inspector is currently not aware of this structure's location, then EHS recommends that they be informed. |
|
27
|
2
|
Equipment room: filter backwash discharged through an air gap |
No |
No
|
No |
Filter backwash pipe turns down into sump. ** Filter backwash wash water should discharge through a complete air gap. |
|
29
|
2
|
Dressing and sanitary facilities: required fixtures provided, clean, and in good repair |
No |
No
|
No |
-- Men's toilet flush valve is broken. ** Replace valve before pool opening day.
-- Hot water at lavatories in restrooms is 113.7F.
** Maximum temperature allowed is 110F. |
|
30
|
2
|
Dressing and sanitary facilities: approved water source, no cross connections |
No |
No
|
No |
Hose bib located beside shower (on outside of main building) and hose bib (at back of building) both lack back flow protection. ** Install vacuum breakers on these hose bibs.
Note: If the 3 free standing hose bibs located at the edge of the pool deck near fence lines are ever put into use (all spigots lack knobs), then vacuum breakers must be installed. |