Premises: body hook and ring buoy with throw rope or lifeguard with rescue tube provided and properly located |
No |
No
|
No |
.2530(a) Provide ring buoy for rope 1.5 times the width of the pool or 50 ft whichever is less.
Buoy rope was greater then 29 feet long. Operator cut the rope and corrected the issue. Rope is now 29 feet long. |
|
17
|
4
|
Premises: decks unobstructed, properly drained, free of trip hazards |
No |
No
|
No |
.2522(a) Provide 6 ft of clear walking space around the pool at all times.
Chairs and tables were less then 6 feet from the pool edge. Operator moved the chairs and tables to meet the 6 feet requirement. |
|
25
|
2
|
Equipment room: equipment and chemicals kept in a dry, well-ventilated enclosure |
No |
No
|
No |
.2533(d) Pump room floor shall be kept dry and free of standing water.
Observed small leak in the pump room. |
|
6
|
6
|
Submerged suction outlets meet ASME/ANSI A112.19.8-2007. Single drains protected. (.2537, .2539) GPM= ____Field verification complete=____ |
No |
No
|
No |
.2539(d) All drain covers shall be kept in good condition. Missing, broken, or cracked fittings shall be replaced or reattached before the pool should be used.
The three required equalizers were missing from the pool. The operator had the correct equalizers in the pool storage area. He securely attached them to the pool. Corrected the issue. |