Pool maintenance: surface skimmers (with weirs, baskets and covers) or gutters clean, in good repair, and functioning properly, no floating debris |
No |
No
|
No |
.2518(k) Replace missing weirs. Observed one missing weir. Due to age of pool not possible to replace. |
|
16
|
4
|
Premises: fence or barrier with self-closing, self-latching gates properly constructed and maintained |
No |
No
|
No |
.2528(a) Ground level doors shall be self-closing, self-latching or child protected by audible alarm. Observed rear door of office area opening to pool deck self-closing but not self-latching and alarm did not work when tested. CDI, alarm repaired.
.2528(b) Maintain no greater than 4" under fence and/or gate (pre-May 2010). Observed greater than 4 inches under fence in some areas measuring 13 inches from grade to bottom horizontal. Pre-2010 construction. |
|
25
|
2
|
Equipment room: equipment and chemicals kept in a dry, well-ventilated enclosure |
No |
No
|
No |
.2533(a) The equipment room door shall have a permanent lock and be kept locked when not in use by the pool operator. Door not able to completely shut and lock.
.2533(b) Provide sufficient lighting in pump room. Light not working in pump room.
.2533(e) Provide continuous forced ventilation or cross ventilation in pump room. Observed no continuous or forced ventilation. |