| Violation Item
| Demerits
| Violation Description
| CDI | R | VR |
|
|
5
|
4
|
Water quality: daily written records of water quality and test kit kept on site |
No |
No
|
No |
Main drain checks not recorded daily. Record daily.
.2535(11) Provide record keeping including daily records of disinfectant residual, pH, drain cover/grate inspections, pool water maintenance, and temperature, if applicable. Provide weekly recordings for cyanuric acid and total alkalinity weekly.
Chemical recordings so same value for cyanuric acid and alkalinity every day. Ensure weekly record keeping for total alkalinity and cyanuric acid. Acid reading recorded at 100 ppm which is limit for cyanuric acid. Tested during inspection at 80 ppm. Maintain accurate record keeping. |
|
11
|
2
|
Pool maintenance: diving equipment, ladders, steps and handrails properly placed, in good repair |
No |
No
|
No |
Greater than 6" from ladder run to wall.
.2521(b) Distance between wall and ladder rung shall range 3" to 6" measured from wall. |
|
13
|
4
|
Pool maintenance: contrasting band on steps and benches |
No |
No
|
No |
Pool steps not built per Code. Pool built in 1985. Bottom step is not a uniform step and has slope to pool floor. Pool steps shall have no greater than 2" difference rise. .2521. |
|
15
|
6
|
Premises: body hook and ring buoy with throw rope or lifeguard with rescue tube provided and properly located |
No |
No
|
No |
Body hook not attached to pole. Correted during inspection.
.2530(a) Provide at least 12 ft. long pole with body hook securely attached. |
|
16
|
4
|
Premises: fence or barrier with self-closing, self-latching gates properly constructed and maintained |
No |
No
|
No |
Electrical/HVAC unit outside of pool barrier provides foothold. Eliminate foothold. Pool built pre-2010.
Windows on to pool deck not permanently affixed. Screws removed. Corrected during inspection to be closed with screws.
One gate by equipment room self-closing, but does not self-latch. Per operator, gate is maintenance gate only and is kept locked at all times.
.2537(b) All gates and doors shall be self-closing, self-latching. |
|
17
|
4
|
Premises: decks unobstructed, properly drained, free of trip hazards |
No |
No
|
No |
Some minor damage to coping in one location. Continue to monitor. If worses to sharp edge or greater than 1/2", repair. Minor damage at deck drain near door entry off fitness room. Deck drain not flush to pool deck next to building. Does not present a hazard to public due to location.
.2537(2) Decks shall be kept free of trip hazards or offsets greater than 1/2" due to deterioration or changes from original deck profile.
.2537(3) There shall be no loose coping. |
|
27
|
2
|
Equipment room: filter backwash discharged through an air gap |
No |
No
|
No |
Backwash line goes directly to drain.
.2513(b) Filter backwash shall be discharged through an air gap. |
|
29
|
2
|
Dressing and sanitary facilities: required fixtures provided, clean, and in good repair |
No |
No
|
No |
No soap or paper towels in restrooms. Mirrors could not be verified as shatterproof. Water in restrooms >110 F.
.2626(j) Provide soap and soap dispenser, no glass, at each sink.
.2626(k) Provide shatterproof mirrors.
.2626(i) Water in restrooms shall not exceed 110 F. |
|
30
|
2
|
Dressing and sanitary facilities: approved water source, no cross connections |
No |
No
|
No |
Pool fill being completed with hose.
.2512(b) Water introduced into the pool, either directly or by the circulation system, shall be supplied through an air gap, anti-siphon vacuum breaker, or backflow preventer.
No backflow prevention device on hose bib in pump room. .2512(a) Water supply serving the swimming pool and all plumbing fixtures shall be an approved water supply. |