11
|
2
|
Pool maintenance: diving equipment, ladders, steps and handrails properly placed, in good repair |
No |
No
|
No |
Observed an end cap missing on a ladder. Replace. |
|
12
|
4
|
Pool maintenance: inlets and other fittings in place and in good repair |
No |
No
|
No |
Observed an eyelet missing. Replace. |
|
22
|
6
|
Premises: emergency telephone provided |
No |
No
|
No |
Observed no directions for the emergency phone. CDI- Wrote Dial 911 on the board.-27. GENERAL COMMENT: No air gap present in the pump room. Observed no water flowing through the sight glass when Travis backwashed the system. A follow up visit will be done. |
|
25
|
2
|
Equipment room: equipment and chemicals kept in a dry, well-ventilated enclosure |
No |
No
|
No |
Observed the floor wet in the pump room. |
|
29
|
2
|
Dressing and sanitary facilities: required fixtures provided, clean, and in good repair |
No |
No
|
No |
Observed water at the restroom handsinks at 138F. Maximum water temp is 110F. |
|
30
|
2
|
Dressing and sanitary facilities: approved water source, no cross connections |
No |
No
|
No |
Observed no backflow preventer in the restrooms. Provide. |