3
|
6
|
Water quality: pool water pH |
No |
No
|
No |
.2535(1) Maintain pH at 7.2 to 7.8. Observed pH at 7.0 at beginning of inspection. CPO added soda ash to pool. EHS observed pH still at 7.0 at end of inspection. Permit denied |
|
24
|
4
|
Equipment room: approved pump, filter, and flow meter operating properly |
No |
No
|
No |
.2518(b) The water circulation system shall circulate and filter the entire volume of public swimming pool water four times or more in 24 hours. The water circulation system shall be operated 24 hours per day at no more than the maximum velocity allowed under Paragraph (d) of this Rule during the operating dates set out in the permit. Observed flow meter reading 30 gpm during inspection. Facility has a permit restriction stating flow is required at 63gpm. Permit denied
.2518(g) Keep flow meter operational. Observed flow meter stuck during inspection. Facility does have a permit restriction. Permit denied. |