| Violation Item
| Demerits
| Violation Description
| CDI | R | VR |
|
|
2
|
6
|
Water quality: disinfectant residual provided by |
No |
No
|
No |
.2535(4) Maintain chlorine at least 1.0 ppm Chlorine had a reading of 0.0ppm. |
|
3
|
6
|
Water quality: pool water pH |
No |
No
|
No |
.2535(1) Maintain pH at 7.2 to 7.8. PH reading observed at 6.6 |
|
5
|
4
|
Water quality: daily written records of water quality and test kit kept on site |
No |
No
|
No |
.2535 (11) The pool operator shall inspect the pool at least daily and maintain written records. No records being kept currently. |
|
8
|
4
|
Pool maintenance: surface skimmers (with weirs, baskets and covers) or gutters clean, in good repair, and functioning properly, no floating debris |
No |
No
|
No |
.2518(k) Keep skimmers free of debris so skimmers are capable of operating per manufacturer instruction. Observed debris left inside of the surface skimmers. |
|
11
|
2
|
Pool maintenance: diving equipment, ladders, steps and handrails properly placed, in good repair |
No |
No
|
No |
.2521(b) Distance between wall and ladder rung shall range 3" to 6" measured from wall. Observed ladder greater than 6 inches away from the pool wall. |
|
12
|
4
|
Pool maintenance: inlets and other fittings in place and in good repair |
No |
No
|
No |
.2537(8) Fittings and/or face plates shall be replaced when damaged and kept in good repair. Observed two inlets covers missing. |
|
15
|
6
|
Premises: body hook and ring buoy with throw rope or lifeguard with rescue tube provided and properly located |
No |
No
|
No |
.2530(a) Provide ring buoy for rope 1.5 times the width of the pool or 50 ft whichever is less. Observed ring buoy rope at 50 feet. Rope was cut to 30 feet during the inspection.
.2530(a) Pole for body hook must be non-telescoping, non-adjustable, and non-collapsible. Body hook pole was adjustable. Replace pole used for body hook. |
|
17
|
4
|
Premises: decks unobstructed, properly drained, free of trip hazards |
No |
No
|
No |
.2522(a) Provide 6 ft of clear walking space around the pool at all times. Pool furniture observed too close to pools. Move to meet clearance space needed. |
|
25
|
2
|
Equipment room: equipment and chemicals kept in a dry, well-ventilated enclosure |
No |
No
|
No |
.2533(a) Pump room shall be weatherproof with a minimum ceiling height of 7 ft.
.2533(b) Provide sufficient lighting in pump room.
.2534(1) Chemical storage room shall be weatherproof with a minimum ceiling height of 7 ft.
.2534(6) Provide sufficient lighting in chemical storage room.
Observed blown bulb in chemical/equipment room. Observed damaged walls and ceiling. Repair damaged ceiling. |
|
29
|
2
|
Dressing and sanitary facilities: required fixtures provided, clean, and in good repair |
No |
No
|
No |
.2526(m) Keep restrooms and fixtures clean and in good repair.
.2526(k) Provide shatterproof mirrors.
Observed restrooms in need of additional cleaning. Observed glass mirrors. |