25
|
2
|
Equipment room: equipment and chemicals kept in a dry, well-ventilated enclosure |
No |
No
|
No |
Forced air vent in chemical/ equipment room not in operation. CPO reports fan runs according to thermostat/ room temperature. Room has no natural cross draft ventilation. ** Forced air fan should run continuously. |
|
29
|
2
|
Dressing and sanitary facilities: required fixtures provided, clean, and in good repair |
No |
No
|
No |
Hot water ~126F @ lavatories in restrooms. ** Maxmum allowed is 110F. |