2
|
6
|
Water quality: disinfectant residual provided by |
No |
No
|
No |
Observed chlorine at 0.7 ppm. CDI, operator adjusted chlorine to 3.0ppm |
|
3
|
6
|
Water quality: pool water pH |
No |
No
|
No |
Observed ph above 8.4 CDI, operator adjusted ph to 7.5. |
|
11
|
2
|
Pool maintenance: diving equipment, ladders, steps and handrails properly placed, in good repair |
No |
No
|
No |
Observed end cap ladder caps missing from a ladder. |
|
25
|
2
|
Equipment room: equipment and chemicals kept in a dry, well-ventilated enclosure |
No |
No
|
No |
.2533(b) Provide sufficient lighting in pump room.
.2533(d) Pump room floor shall be kept dry and free of standing water. |
|
27
|
2
|
Equipment room: filter backwash discharged through an air gap |
No |
No
|
No |
.2513(b) Filter backwash shall be discharged through an air gap. |
|
29
|
2
|
Dressing and sanitary facilities: required fixtures provided, clean, and in good repair |
No |
No
|
No |
.2626(m) Keep restrooms and fixtures clean and in good repair.
Observed no soap in restrooms. |
|
33
|
2
|
Dressing and sanitary facilities: hose bibbs and floor drains provided |
No |
No
|
No |
Observed no backflow prevention device on hose bib. |