| Violation Item
| Demerits
| Violation Description
| CDI | R | VR |
|
|
6
|
6
|
Submerged suction outlets meet ASME/ANSI A112.19.8-2007. Single drains protected. (.2537, .2539) GPM= ____Field verification complete=____ |
No |
No
|
No |
.2539(b) Pools with single main drain or drains <36" apart shall provide a safety vacuum release system (SVRS) or other methods of preventing bather entrapment. Observed no SVRS system in place on pool. PDSC form shows a Vac-Alert VA 2000 is installed. EHS observed installation area for Vac-Alert is capped off and Vac-Alert has been removed. |
|
8
|
4
|
Pool maintenance: surface skimmers (with weirs, baskets and covers) or gutters clean, in good repair, and functioning properly, no floating debris |
No |
No
|
No |
.2518(k) Replace missing weirs. Observed 3 missing weirs.
.2518(k) Surface skimmers shall be installed per manufacturer's instructions. Observed one weir stuck and unable to freely move. |
|
11
|
2
|
Pool maintenance: diving equipment, ladders, steps and handrails properly placed, in good repair |
No |
No
|
No |
.2521 Install ladders per manufacturer instructions. 1 ladder is very loose. Install ladder to manufacturer’s instructions. REPEAT VIOLATION |
|
15
|
6
|
Premises: body hook and ring buoy with throw rope or lifeguard with rescue tube provided and properly located |
No |
No
|
No |
.2530(a) Provide USCG approved ring buoy. A rescue tube with lifeguard may be substituted for ring buoy. Observed ring buoy where anchors are loose and rope is frayed and dry rotted. |
|
16
|
4
|
Premises: fence or barrier with self-closing, self-latching gates properly constructed and maintained |
No |
No
|
No |
.2528(a) Ground level doors shall be self-closing, self-latching or child protected by audible alarm. Observed 2 doors on pool deck with no working alarms. |
|
17
|
4
|
Premises: decks unobstructed, properly drained, free of trip hazards |
No |
No
|
No |
.2537(2) Decks shall be kept in good repair. Observed decking in front of ladder is damaged and sharp. Damaged area is approximately 8” around. |
|
18
|
4
|
Premises: lifeguards present or warning signs posted |
No |
No
|
No |
.2530(c) Provide "Children should not use the swimming pool without adult supervision." in 1" lettering. Observed no signage with aforementioned statement. |
|
22
|
6
|
Premises: emergency telephone provided |
No |
No
|
No |
.2530(f) Signage with legible letters providing dialing instructions, address of pool and pool telephone number shall be posted at the emergency phone. Observed no address or phone number posted for emergency phone. |
|
27
|
2
|
Equipment room: filter backwash discharged through an air gap |
No |
No
|
No |
.2513(b) Filter backwash shall be discharged through an air gap. No air gap between backwash pit and bottom of pipe. REPEAT VIOLATION |