15
|
6
|
Premises: body hook and ring buoy with throw rope or lifeguard with rescue tube provided and properly located |
No |
No
|
No |
.2530(a) Provide USCG approved ring buoy. A rescue tube with lifeguard may be substituted for ring buoy. Ring buoy is not USCG approved. CDI - CPO purchased and provided new USCG approved ring buoy from local pool supply store.
.2530(a) Provide ring buoy with rope 1.5 times the width of the pool or 50 ft whichever is less. Throw rope is freyed and likely to break during use. CDI - Rope replaced. |
|
16
|
4
|
Premises: fence or barrier with self-closing, self-latching gates properly constructed and maintained |
No |
No
|
No |
.2528(a) Provide no openings in fence and/or gate greater than 4"x4". Some screws holding vertical portions of fence are missing causing vertical members to fall to one side and creating 6 to 8 inch gaps in fence. CDI - All vertical members secured with screws. |
|
24
|
4
|
Equipment room: approved pump, filter, and flow meter operating properly |
No |
No
|
No |
.2518(g) Keep flow meter operational. Bobber in flow meter stuck. CDI - Flow meter repaired by maintenance during the inspection. |
|
27
|
2
|
Equipment room: filter backwash discharged through an air gap |
No |
No
|
No |
.2513(b) Filter backwash shall be discharged through an air gap. Discharge line is directly plumbed with no air gap. Site glass is provided. |