5
|
4
|
Water quality: daily written records of water quality and test kit kept on site |
No |
No
|
No |
No recent Cyanuric Acid recordings in the pool log book. Check daily Cl, pH, main drains and record any daily pool maintenance activities. Record at least weekly Total Alkalinity and Cyanuric Acid. CYA tested today at 80ppm. |
|
17
|
4
|
Premises: decks unobstructed, properly drained, free of trip hazards |
No |
No
|
No |
Standing water on pool deck. Not sloped to drain. Ensure that pool deck is sloped to drain. |
|
24
|
4
|
Equipment room: approved pump, filter, and flow meter operating properly |
No |
No
|
No |
Flow meter stuck. Corrected by operator. |
|
27
|
2
|
Equipment room: filter backwash discharged through an air gap |
No |
No
|
No |
Provide air gap for backwash. |
|
28
|
2
|
Dressing and sanitary facilities: bathhouse or rest rooms accessible; shower sign posted |
No |
No
|
No |
Provide signage directing bathers to shower before entering the pool. |
|
29
|
2
|
Dressing and sanitary facilities: required fixtures provided, clean, and in good repair |
No |
No
|
No |
Hot water > 110F. Maintain water at no more than 110F.
Sink slowly drains in restroom. Maintain sink and drain in good working order. |
|
33
|
2
|
Dressing and sanitary facilities: hose bibbs and floor drains provided |
No |
No
|
No |
No floor drain in restroom. |