| Violation Item
| Demerits
| Violation Description
| CDI | R | VR |
|
|
3
|
6
|
Water quality: pool water pH |
No |
No
|
No |
pH 7.0. Maintain between 7.2 and 7.8. |
|
5
|
4
|
Water quality: daily written records of water quality and test kit kept on site |
No |
No
|
No |
No cyanuric acid or total alkalinity checks. Check at least weekly. |
|
6
|
6
|
Submerged suction outlets meet ASME/ANSI A112.19.8-2007. Single drains protected. (.2537, .2539) GPM= ____Field verification complete=____ |
No |
No
|
No |
Equalizer line cover sticks out into the pool > 2 inches. Install A112 approved equalizer line cover.Current PDSC form not approved. Provide approved Pool Drain Safety form. |
|
8
|
4
|
Pool maintenance: surface skimmers (with weirs, baskets and covers) or gutters clean, in good repair, and functioning properly, no floating debris |
No |
No
|
No |
Both weirs missing. Install functional weirs. |
|
9
|
4
|
Pool maintenance: depth markings and no diving markers or signs visible and properly located |
No |
No
|
No |
Some no diving markers are not the international no diving marker. Provide either the international no diving symbol on a 6x6 inch tile or the words NO DIVING in at least four inch lettering. These shall be no more than 25 feet apart. |
|
15
|
6
|
Premises: body hook and ring buoy with throw rope or lifeguard with rescue tube provided and properly located |
No |
No
|
No |
Ring buoy deteriorated, throw rope not attached, only 31 feet long. Provide US Coast Guard approved ring buoy with a 33 foot throw rope. |
|
17
|
4
|
Premises: decks unobstructed, properly drained, free of trip hazards |
No |
No
|
No |
Deck chairs too close to pool edge. Provide at least 6 feet clear walkway around the pool. |
|
22
|
6
|
Premises: emergency telephone provided |
No |
No
|
No |
No phone number posted at emergency phone. Post phone number for emergency phone. |
|
24
|
4
|
Equipment room: approved pump, filter, and flow meter operating properly |
No |
No
|
No |
Flow meter stuck. Repair or replace. |
|
25
|
2
|
Equipment room: equipment and chemicals kept in a dry, well-ventilated enclosure |
No |
No
|
No |
Fan in pump room not functioning. Provide functional fan. |
|
27
|
2
|
Equipment room: filter backwash discharged through an air gap |
No |
No
|
No |
Provide air gap for backwash. |
|
29
|
2
|
Dressing and sanitary facilities: required fixtures provided, clean, and in good repair |
No |
No
|
No |
Hot water > 110F. Maintain at 110F or less. |