| Violation Item
| Demerits
| Violation Description
| CDI | R | VR |
|
|
7
|
4
|
Pool maintenance: pool walls and floor kept clean, free of debris and in good repair |
No |
No
|
No |
Some chipping paint on pool walls. Paint has not chipped off to present a hazard to the public at time of inspection. Continue to monitor and patch/repair as needed. May require permanent repair in the future if worsens. |
|
11
|
2
|
Pool maintenance: diving equipment, ladders, steps and handrails properly placed, in good repair |
No |
No
|
No |
Ladder rungs >6" from pool wall. Original construction. Ensure ladder rungs 3" to 6" from pool wall. |
|
15
|
6
|
Premises: body hook and ring buoy with throw rope or lifeguard with rescue tube provided and properly located |
No |
No
|
No |
Two ring buoys on pool deck. One with grab rope starting to degrade. Removed from pool deck during the inspection. Pool is only required one ring buoy with rope per NC Rule requirement. |
|
16
|
4
|
Premises: fence or barrier with self-closing, self-latching gates properly constructed and maintained |
No |
No
|
No |
Ledge at fence tie into building provides foothold. Pool built pre-2010. Eliminate foothold. |
|
17
|
4
|
Premises: decks unobstructed, properly drained, free of trip hazards |
No |
No
|
No |
Pebbled deck used that has been sealed. Seal starting to degrade in some locations. May require repair in future if worsens.
Some small offsets at tie into deck and coping. No offsets greater than 1/2" or that could present a trip hazard at time of inspection. Continue to monitor. May require repair if worsens. |
|
22
|
6
|
Premises: emergency telephone provided |
No |
No
|
No |
Emergency phone with incorrect phone number. Signage corrected during the inspection and reposted to read correct address and phone number. Phone rings back to front desk and was answered by front desk during inspection. Management stated front desk is staffed 24/7. Phone can ring back to front desk as long as phone is monitored during pool hours. |
|
24
|
4
|
Equipment room: approved pump, filter, and flow meter operating properly |
No |
No
|
No |
Leak at valve on skimmer line. Repair leak. Does not appear to be substantial enough to effect pool quality. |
|
25
|
2
|
Equipment room: equipment and chemicals kept in a dry, well-ventilated enclosure |
No |
No
|
No |
Floor wet in pump room due to leak at skimmer line. Keep equipment room floor dry. |
|
27
|
2
|
Equipment room: filter backwash discharged through an air gap |
No |
No
|
No |
No air gap at backwash line. Original construction. Filter shall be backwashed through air gap. |
|
29
|
2
|
Dressing and sanitary facilities: required fixtures provided, clean, and in good repair |
No |
No
|
No |
Hot water in pool restroom >113 F. Maintain at 110 F or below.
Mirror in restroom could not be verified as shatterproof. Mirrors shall be shatterproof in restrooms. |
|
30
|
2
|
Dressing and sanitary facilities: approved water source, no cross connections |
No |
No
|
No |
No hose bib on hose bib in pump room or on pool deck. Provide backflow prevention device.
No check valve on fill line. Original construction. Water shall be introduced into the pool through a check valve per .2512. |
|
33
|
2
|
Dressing and sanitary facilities: hose bibbs and floor drains provided |
No |
No
|
No |
No floor drain or hose bib in pool restroom. Original construction. |