Select your filters and click the Search button to search for data, or click Clear to clear all filters
 
Logo Main Menu
Mecklenburg County Health Dept
Public Health Inspections
Select your filters and click the Search button to search for data, or click Clear to clear all filters
 
  
 

Premises Information

Return to Inspections
NameHOBBS RIDGE
Address3724 SELWYN FARMS LN
 
City/State/ZIP
CHARLOTTE NC 28209
Premise Type50 - Seasonal Swimming Pool
CountyMecklenburg
Inspection Date 4/23/2025
Final Score @ Grade
10
General CommentsInspection with CPO, Pierce Sawyer No night swimming Permit Restriction: Flow meter must remain operable. Flow required at 89 GPM to 100 GPM to meet turnover and flow restriction of the filter. Observed flow at 90 GPM. EHS verified: Operable blue white flow meter installed in 2” line Main drain, skimmer, and return line all with 2” pipe (2) Aquastar A10RCFRxxx 2008 main drain covers (3) Aquastar A10RCFRxxx 2008 EQ line covers Pentair TR100 filter rated for 100 GPM 6 returns installed on pool wall

Violations

 
CDI=Corrected During Inspection  R=Repeat Violation  VR=Verification Required 
Violation Item Demerits Violation Description CDIRVRComments
7 4 Pool maintenance: pool walls and floor kept clean, free of debris and in good repair No No No .2537(14) Keep pool surface and pool floor free of debris. Observed minor pollen/dirt residue in the middle of the pool floor.
16 4 Premises: fence or barrier with self-closing, self-latching gates properly constructed and maintained No No No .2528(a) Provide no openings in fence and/or gate greater than 4"x4". Observed bend in fence that was 6”. CDI-CPO corrected bend in fence to be 4”.
27 2 Equipment room: filter backwash discharged through an air gap No No No .2513(b) Filter backwash shall be discharged through an air gap. Observed backwash pipe without an air gap.