Select your filters and click the Search button to search for data, or click Clear to clear all filters
 
Logo Main Menu
Mecklenburg County Health Dept
Public Health Inspections
Select your filters and click the Search button to search for data, or click Clear to clear all filters
 
  
 

Premises Information

Return to Inspections
NameHIGHLANDS APARTMENTS
Address639 ARCHDALE DRIVE
 
City/State/ZIP
CHARLOTTE NC 28217
Premise Type50 - Seasonal Swimming Pool
CountyMecklenburg
Inspection Date 7/7/2023
Final Score @ Grade
24
General CommentsIssued permit. No Night Swimming.

Violations

 
CDI=Corrected During Inspection  R=Repeat Violation  VR=Verification Required 
Violation Item Demerits Violation Description CDIRVRComments
5 4 Water quality: daily written records of water quality and test kit kept on site No No No Test kit with expired reagents, not giving accurate chlorine reading. .2535(10) Provide test kit capable of measuring disinfectant level, cyanuric acid and total alkalinity. Operator has strips and manager ordered test kit while onsite. Corrected.
8 4 Pool maintenance: surface skimmers (with weirs, baskets and covers) or gutters clean, in good repair, and functioning properly, no floating debris No No No One weir missing at time of inspection. .2518(k) Replace missing weirs. Operator replaced and corrected.
16 4 Premises: fence or barrier with self-closing, self-latching gates properly constructed and maintained No No No Gate not latching at time of inspection. .2528(a) Access gates shall swing away from the pool and be self-latching, self-closing unless an attendant AND lifeguard are present. Operator corrected gate to self-close, self-latch.
23 4 Equipment room: chlorine or bromine automatic feeders that meet NSF Standard 50 No No No Feeder not shutting off flow with pump at time of inspection. .2535(6) Automatic chlorine and acid feeder pumps shall be automatically prevented from operating when the circulation pump is not in operation. Operator adjusted breaker for feeder to shut off with pump. Corrected.
25 2 Equipment room: equipment and chemicals kept in a dry, well-ventilated enclosure No No No Liquid chemicals in pump room. Dry chemicals stored in separate shed. No clearance around piping. Original construction. .2534(2) Pools constructed after April 1, 2004 shall provide a separate room for chemical storage meeting Rule.2534. .2533(c) Valves and controls shall be accessible to the pool operator at all times. Maintain 3 ft. clear walking space in pump room.
26 2 Equipment room: valves and pipes identified by color codes or labels No No No Piping not labeled. .2518(d) Piping and valves shall be labeled with color codes or labels.
27 2 Equipment room: filter backwash discharged through an air gap No No No No air gap at backwash. .2513(b) Filter backwash shall be discharged through an air gap.
33 2 Dressing and sanitary facilities: hose bibbs and floor drains provided No No No No floor drain in restroom. .2526(c) Floor drains shall be provided in restrooms.