6
|
6
|
Submerged suction outlets meet ASME/ANSI A112.19.8-2007. Single drains protected. (.2537, .2539) GPM= ____Field verification complete=____ |
No |
No
|
No |
.2539(c) All pools, prior to permit issuance, shall provide documentation to the Department to verify suction outlet safety compliance. EHS observed equalizer information on PDSC form to not match what is actually in the pool. Resubmit accurate PDSC form for approval. |
|
15
|
6
|
Premises: body hook and ring buoy with throw rope or lifeguard with rescue tube provided and properly located |
No |
No
|
No |
.2530(a) Provide ring buoy for rope 1.5 times the width of the pool or 50 ft whichever is less. Observed rope length exceeding 50ft. Rope length was cut to required length during inspection |
|
16
|
4
|
Premises: fence or barrier with self-closing, self-latching gates properly constructed and maintained |
No |
No
|
No |
.2528(b) Maintain no greater than 4" under fence and/or gate (pre-May 2010). Observed 7 inch gap under fence closest to road.
.2528(a) Provide no openings in fence and/or gate greater than 4"x4". Observed fencing behind retaining wall facing apartments with 6” gap between verticals. Pool is pre 2010 |