9
|
4
|
Pool maintenance: depth markings and no diving markers or signs visible and properly located |
No |
No
|
No |
Observed depth markings on the pool deck painted over and no longer visible. Operator was able to template and paint the depth markings during inspection. |
|
15
|
6
|
Premises: body hook and ring buoy with throw rope or lifeguard with rescue tube provided and properly located |
No |
No
|
No |
Rope at time of inspection was measured at 58 feet. Rope length required as calculated by PEHS staff is 18 feet. Rope cut down to 18 Feet |
|
17
|
4
|
Premises: decks unobstructed, properly drained, free of trip hazards |
No |
No
|
No |
Observed several pool chairs 3-4 feet from the pool edge. Maintain at least 6 feet of distance from the pool edge. |