| Violation Item
| Demerits
| Violation Description
| CDI | R | VR |
|
|
2
|
6
|
Water quality: disinfectant residual provided by |
No |
No
|
No |
Less than 1 ppm chlorine at time of inspection. .2535(4) Maintain chlorine at least 1.0 ppm. Chlorinator must work.
*Permit item |
|
9
|
4
|
Pool maintenance: depth markings and no diving markers or signs visible and properly located |
No |
No
|
No |
‘No Diving’ faded at 5’ by depth change. .2523(d) No Diving markers shall be provided in all areas of the pool less than five feet deep.
.2523(d) No Diving markers shall be written in four inch letters or international 6"x6" no diving in red and black on a white background.
*Permit item |
|
11
|
2
|
Pool maintenance: diving equipment, ladders, steps and handrails properly placed, in good repair |
No |
No
|
No |
Ladder missing slip-resistant tread. .2521(b) Ladders shall have slip-resistant tread. |
|
12
|
4
|
Pool maintenance: inlets and other fittings in place and in good repair |
No |
No
|
No |
Inlet fittings missing. .2537(8) Fittings and/or face plates shall be replaced when damaged and kept in good repair.
*Permit item ' |
|
15
|
6
|
Premises: body hook and ring buoy with throw rope or lifeguard with rescue tube provided and properly located |
No |
No
|
No |
Buoy rope too long at time of inspection.
.2530(a) Provide ring buoy for rope 1.5 times the width of the pool or 50 ft whichever is less. Operator cut and corrected to 38’. |
|
16
|
4
|
Premises: fence or barrier with self-closing, self-latching gates properly constructed and maintained |
No |
No
|
No |
Doors onto pool deck (top area of clubhouse with deck that leads to stairs and gate not latching to pool) not self-closing, self-latching. Renovations done to clubhouse. Either doors onto pool “deck area” or gate at top of stairs to pool need to be in compliance for permit. Windows onto pool area open more than 4”. .2528(a) Ground level doors shall be self-closing, self-latching or child protected by audible alarm.
.2528(a) Ground level windows shall not open greater than 4" on to pool deck or child protected by audible alarm.
*Permit item.
One piece of fencing with gap greater than 4”. Pool built 1972.
.2528(a) Provide no openings in fence and/or gate greater than 4"x4".
.2537(b) All gates and doors shall be self-closing, self-latching. |
|
17
|
4
|
Premises: decks unobstructed, properly drained, free of trip hazards |
No |
No
|
No |
Deck starting to fall in some areas, creating offsets greater than 1/2”. .2522(a) Provide 6 ft of clear walking space around the pool at all times.
.2537(2) Decks shall be kept free of trip hazards or offsets greater than 1/2" due to deterioration or changes from original deck profile.
*Must be corrected for 2024 permit |
|
21
|
4
|
Premises: pool and deck lighting provided at pools that operate at night |
No |
No
|
No |
Both lighting fixtures missing on walls of pool, leaving holes in pool wall. .2524(c) Lighting fixtures shall not present a hazard to the public.
.2537(9) Underwater light niches shall be maintained or covered so not to present a hazard.
*Permit item |
|
22
|
6
|
Premises: emergency telephone provided |
No |
No
|
No |
Emergency phone signage missing callback number. .2530(f) Signage with legible letters providing dialing instructions, address of pool and pool telephone number shall be posted at the emergency phone.
*Permit item |
|
23
|
4
|
Equipment room: chlorine or bromine automatic feeders that meet NSF Standard 50 |
No |
No
|
No |
Chlorine out at time of inspection. Unable to check operational. .2535(6) Provide NSF approved automatic chlorinator installed per manufacturer instructions. Must also turn off with pump.
*Permit item |
|
27
|
2
|
Equipment room: filter backwash discharged through an air gap |
No |
No
|
No |
No air gap at backwash. Original construction. .2513(b) Filter backwash shall be discharged through an air gap. |
|
29
|
2
|
Dressing and sanitary facilities: required fixtures provided, clean, and in good repair |
No |
No
|
No |
Restrooms missing soap, toilet paper and towels for hand drying. .2526(j) Provide soap and soap dispenser, no glass, at each sink.
.2526(l) Provide toilet paper and dispensers in restrooms.
.2526(m) Keep restrooms and fixtures clean and in good repair. |
|
30
|
2
|
Dressing and sanitary facilities: approved water source, no cross connections |
No |
No
|
No |
No backflow prevention on hose bib in equipment room. .2512(b) Water introduced into the pool, either directly or by the circulation system, shall be supplied through an air gap, anti-siphon vacuum breaker, or backflow preventer. |
|
33
|
2
|
Dressing and sanitary facilities: hose bibbs and floor drains provided |
No |
No
|
No |
No floor drain in restrooms. Original construction. .2526(c) Floor drains shall be provided in restrooms. |