2
|
6
|
Water quality: disinfectant residual provided by |
No |
No
|
No |
.2535(4) Maintain chlorine at least 1.0 ppm. Observed chlorine not reading on test kit. Measured at 0 ppm. CDI - CPO added shock and increased chlorine to 10. |
|
9
|
4
|
Pool maintenance: depth markings and no diving markers or signs visible and properly located |
No |
No
|
No |
.2523(a) Provide depth markers on pool walls and pool deck next to the swimming pool. Observed a total of 3 faded 5 ft depth markers. CDI - Maintenance corrected so that they are now visible. |
|
15
|
6
|
Premises: body hook and ring buoy with throw rope or lifeguard with rescue tube provided and properly located |
No |
No
|
No |
.2530(a) Provide USCG approved ring buoy. A rescue tube with lifeguard may be substituted for ring buoy. Observed unapproved, residential ring buoy.
.2530(a) Provide ring buoy for rope 1.5 times the width of the pool or 50 ft whichever is less. Observed throw rope attached to a residential ring buoy measuring > 26 ft.
CDI - Both items corrected during inspection. |
|
18
|
4
|
Premises: lifeguards present or warning signs posted |
No |
No
|
No |
.2530(c) Provide "Warning - No Lifeguard on Duty" in 4" lettering. Observed no lifeguard on duty warning sign measuring < 4" in lettering. CDI - CPO procured new signage meeting requirements. |
|
24
|
4
|
Equipment room: approved pump, filter, and flow meter operating properly |
No |
No
|
No |
.2518(g) Keep flow meter operational. Observed flow meter stuck. Repair. |
|
25
|
2
|
Equipment room: equipment and chemicals kept in a dry, well-ventilated enclosure |
No |
No
|
No |
.2533(b) Provide sufficient lighting in pump room. Observed inoperable lighting in pump room. Repair. |