Water quality: daily written records of water quality and test kit kept on site |
No |
No
|
No |
.2535 (4) Lower and maintain cyanuric acid at or below 100 ppm. - Observed cyanuric acid listed as 200ppm daily on records. Lower cyanuric acid levels to 100ppm or below. CPO unable to test cyanuric acid and provide a ppm value during inspection. Ensure correct way to measure cyanuric acid with test kit is being followed. |
|
15
|
6
|
Premises: body hook and ring buoy with throw rope or lifeguard with rescue tube provided and properly located |
No |
No
|
No |
.2530(a) Provide at least 12 ft. long pole with body hook securely attached. - Observed body hook attached to 6ft long pole. - CDI - PIC attached body hook to 12ft long pole during inspection. |
|
23
|
4
|
Equipment room: chlorine or bromine automatic feeders that meet NSF Standard 50 |
No |
No
|
No |
.2535(6) Provide NSF approved automatic chlorinator installed per manufacturer instructions. - Observed installed saltwater chlorinator to be malfunctioning; light flashing that indicates cell needs to be inspected. CPO stated chlorine is being hand fed directly into pool daily. Install an NSF approved automatic chlorinator. Permit denied until chlorinator installed. |
|
27
|
2
|
Equipment room: filter backwash discharged through an air gap |
No |
No
|
No |
.2513(b) Filter backwash shall be discharged through an air gap. - No air gap observed for backwash pipe. Create an air gap. |