Submerged suction outlets meet ASME/ANSI A112.19.8-2007. Single drains protected. (.2537, .2539) GPM= ____Field verification complete=____ |
No |
No
|
No |
Observed Paramount SDX Retro main drain covers but Hayward covers on submitted PDSC form. Re-submit form. Immediate suspension of permit pending approval of PDSC. |
|
8
|
4
|
Pool maintenance: surface skimmers (with weirs, baskets and covers) or gutters clean, in good repair, and functioning properly, no floating debris |
No |
No
|
No |
Observed 2 weirs missing out of 3. Floating debris in skimmers. |
|
15
|
6
|
Premises: body hook and ring buoy with throw rope or lifeguard with rescue tube provided and properly located |
No |
No
|
No |
Bluoy throw rope 55 ft. Trimmed to required 50 ft during inspection. |
|
16
|
4
|
Premises: fence or barrier with self-closing, self-latching gates properly constructed and maintained |
No |
No
|
No |
Observed door from leasing office to pool enclosure not self-latching. One gate swings inward towards pool. Observed more than 2" clearance under section of fence on retaining wall. Appears a wall timber was removed. Observed horizontal fence member less than 45 " from ground around entire perimeter of enclosure. Eliminate footholds less than 45 " from ground. |
|
17
|
4
|
Premises: decks unobstructed, properly drained, free of trip hazards |
No |
No
|
No |
Observed lounge chairs too close to pooledge. Chairs moved. |
|
22
|
6
|
Premises: emergency telephone provided |
No |
No
|
No |
When connected by Kings III to 911 operator, phone number supplied by operator is different from posted number. When stated phone number called from office it was declared disconnected.. Immediate suspension. |