25
|
2
|
Equipment room: equipment and chemicals kept in a dry, well-ventilated enclosure |
No |
No
|
No |
.2533(e) Provide continuous forced ventilation or cross ventilation in pump room. No ventilation in pump room.
.2533(a) Pump room shall be weatherproof with a minimum ceiling height of 7 ft. Ceiling in pump room has caved in and is open to the outside.
.2534(6) Provide sufficient lighting in chemical storage room./.2533(b) Provide sufficient lighting in pump room. No lighting in room. |
|
26
|
2
|
Equipment room: valves and pipes identified by color codes or labels |
No |
No
|
No |
.2518(d) Piping and valves shall be labeled with color codes or labels. No labeling on pipes observed. Corrected during inspection. |
|
27
|
2
|
Equipment room: filter backwash discharged through an air gap |
No |
No
|
No |
.2513(b) Filter backwash shall be discharged through an air gap. No air gap - discharges onto ground. |