Select your filters and click the Search button to search for data, or click Clear to clear all filters
 
Logo Main Menu
Mecklenburg County Health Dept
Public Health Inspections
Select your filters and click the Search button to search for data, or click Clear to clear all filters
 
  
 

Premises Information

Return to Inspections
NameRED ROOF INN LAKE NORMAN
Address20740 TORRENCE CHAPEL ROAD
 
City/State/ZIP
CORNELIUS NC 28031
Premise Type50 - Seasonal Swimming Pool
CountyMecklenburg
Inspection Date 7/9/2024
Final Score @ Grade
38
General CommentsOSV to pool for infield plan review. Verified the following items. Pump approved. 1) New Pump - Hayward Max Flo-XL, W3SP2307x10, 1 hp pump with (2) 2008 Hayward WGX1048E drain covers. 2) Rola-Chem flow meter installed per mfg. instructions with 21" on inlet and 18" on outlet reading 60 gpm. Required inlet/outlet is 20" and 10". 3) Hayward S2443 filter rated for 62 gpm. 4) All pipe - 2" line. 5) (2) skimmers with EQ lines plastered on wall. 6) (3) wall returns. A full inspection was completed at time of visit. Permit denial items: 1) .2530 - Provide new USCG approved ring buoy with 23 ft. rope. Grab rope on current buoy is damaged. Buoy is in disrepair. 2) .2535 - CPO shall be present at property at least daily to maintain pool. 3) .2535 - Provide total alkalinity and cyanuric acid readings once weekly in log book; record main drains checks daily. 4) .2523 - Depth markers on pool wall missing "ft" or "feet". Provide visible on wall depth markers. 5) .2537 - Repair screw in light - coming out and protrudes more than 1/2". 6) .2538 - repair gate to self-close, self-latch or permanently disable if building/fire code ok. 7) .2530 - provide warning no lifeguard on duty in 4" lettering. Once items listed above are corrected, contact Katie to schedule a return inspection. Note - EQ lines are not plugged in skimmer. Not holding debris. T-Cell 3 installed. Approved for 15,000 gallon pools. Pool at 13,913 gallons. Measured during site visit. Salt approved for primary. Recommend obtaining a back-up chlorinator if salt system is ever disabled/damaged.

Violations

 
CDI=Corrected During Inspection  R=Repeat Violation  VR=Verification Required 
Violation Item Demerits Violation Description CDIRVRComments
5 4 Water quality: daily written records of water quality and test kit kept on site No No No CPO not present at time of inspection. CPO shall maintain daily site visits to maintain the pool. Permit Item. Provide record keeping for total alkalinity and cyanuric acid weekly. Provide record keeping for main drains checks daily. Permit item.
7 4 Pool maintenance: pool walls and floor kept clean, free of debris and in good repair No No No Screw protruding from light >1/2". Repair screw in wall. Permit Item. Some damage to the pool paint. Continue to monitor. May require repair if worsens.
9 4 Pool maintenance: depth markings and no diving markers or signs visible and properly located No No No Depth markers on pool wall missing "ft"/worn off. Provide ft or feet on pool wall on all depth markers. Permit Item.
11 2 Pool maintenance: diving equipment, ladders, steps and handrails properly placed, in good repair No No No Ladder rungs 8 1/2" from pool wall. Maintain 3" to 6" from ladder rung to wall. Original construction.
15 6 Premises: body hook and ring buoy with throw rope or lifeguard with rescue tube provided and properly located No No No USCG approved ring buoy with grab rope degraded and damaged. Replace with USCG approved ring buoy. If rope replaced, provide 23 ft. rope. Old rope still ok.
16 4 Premises: fence or barrier with self-closing, self-latching gates properly constructed and maintained No No No REPEAT .2528(a) Access gates shall swing away from the pool and be self-latching, self-closing unless an attendant AND lifeguard are present. Gates observed to swing into pool area per fire egress from main building. .2528(b) Maintain no greater than 4" under fence and/or gate (pre-May 2010). Openings around pool fencing observed greater than 4 inches in some areas. <45" between horizontals on pool barrier. Pool built pre-May2010. One of two entrances kept locked; however, when unlocked, gate does not self-latch. Permanently disable if fire/building ok or repair gate to self-close, self-latch. Permit Item.
18 4 Premises: lifeguards present or warning signs posted No No No Warning No Lifeguard on Duty not large enough lettering. Provide Warning No Lifeguard on Duty in 4" lettering. Permit item.
24 4 Equipment room: approved pump, filter, and flow meter operating properly No No No Small leak at air relief valve on filter. Repair leak. Does not warrant permit action.
25 2 Equipment room: equipment and chemicals kept in a dry, well-ventilated enclosure No No No Light burnt out in pump room. Repair light.
27 2 Equipment room: filter backwash discharged through an air gap No No No No air gap at backwash line to pit. Provide air gap.
30 2 Dressing and sanitary facilities: approved water source, no cross connections No No No No check valve or backflow prevention device on hose bib in pump room. Original construction. Provide ASSE approved check valve and backflow prevention device.