Premises: fence or barrier with self-closing, self-latching gates properly constructed and maintained |
No |
No
|
No |
16) Fencing does not meet current rules. Appears to be pre-2010. Gaps as large as 5" through the fence, fence as short as 36".
Provide fencig at least 48" high with no gaps greater than 4" through the fence.
16) Gates swing into the pool. Appear to be for fire egress. Recommend checking with fire marshall. Gates should swing away from
the pool. |
|
24
|
4
|
Equipment room: approved pump, filter, and flow meter operating properly |
No |
No
|
No |
Flow meter reads more than the filter and multiport are rated for. Operator states it's a new flow meter. .2518(g) Install flow meter on return line per manufacturer instructions. Flow meter shall read within 10% of true flow. |
|
27
|
2
|
Equipment room: filter backwash discharged through an air gap |
No |
No
|
No |
.2513(b) Filter backwash shall be discharged through an air gap. |
|
29
|
2
|
Dressing and sanitary facilities: required fixtures provided, clean, and in good repair |
No |
No
|
No |
Hot water > 110F. .2626(i) Water in restrooms shall not exceed 110 F. |
|
33
|
2
|
Dressing and sanitary facilities: hose bibbs and floor drains provided |
No |
No
|
No |
.2626(d) Provide hose bib so that all parts of restroom can be reached with a 50 ft hose.
.2626(c) Floor drains shall be provided in restrooms. |