2
|
6
|
Water quality: disinfectant residual provided by |
No |
No
|
No |
Observed Cl at 0.4ppm.
.2535(4) Maintain chlorine at least 1.0 ppm. |
|
6
|
6
|
Submerged suction outlets meet ASME/ANSI A112.19.8-2007. Single drains protected. (.2537, .2539) GPM= ____Field verification complete=____ |
No |
No
|
No |
PDSC form incorrect, skimmer equalizers plugged. Unplug equalizer lines or update PDSC.
.2539(c) All pools, prior to permit issuance, shall provide documentation to the Department to verify suction outlet safety compliance.
Observed skimmer equalizers sticking out from wall at shallow end equalizer and equalizer on side of pool opposite of gate.
.2537(7) Drain covers shall be in good condition and securely attached.
.2539(b) All suction fittings shall be installed in accordance with the manufacturer's instructions. |
|
11
|
2
|
Pool maintenance: diving equipment, ladders, steps and handrails properly placed, in good repair |
No |
No
|
No |
Ladder missing end caps. Replace.
.2521 Install ladders per manufacturer instructions. |
|
16
|
4
|
Premises: fence or barrier with self-closing, self-latching gates properly constructed and maintained |
No |
No
|
No |
Observed fence and gate replaced, installed 2019.
Gate not self closing, gate is getting hung on ground.
.2537(b) All gates and doors shall be self-closing, self-latching.
Observed gate with 5 1/2" from ground.
Observed fence over 2" from ground throughout.
.2528(a) Maintain 2" or less under fence and/or gate (post-May 2010). |
|
22
|
6
|
Premises: emergency telephone provided |
No |
No
|
No |
Observed no emergency phone signage. Corrected during inspection.
.2530(f) Signage with legible letters providing dialing instructions, address of pool and pool telephone number shall be posted at the emergency phone. |
|
24
|
4
|
Equipment room: approved pump, filter, and flow meter operating properly |
No |
No
|
No |
Observed flow meter stuck.
.2518(g) Keep flow meter operational. |