Submerged suction outlets meet ASME/ANSI A112.19.8-2007. Single drains protected. (.2537, .2539) GPM= ____Field verification complete=____ |
No |
No
|
No |
.2539(c) All pools, prior to permit issuance, shall provide documentation to the Department to verify suction outlet safety compliance. Observed pool flow rate at 55gpm. Permit restriction requires pump to be set to 66gpm to 80 GPM to meet turnover and flow restriction for # of returns . Permit denied and pool placed on Q status. |
|
7
|
4
|
Pool maintenance: pool walls and floor kept clean, free of debris and in good repair |
No |
No
|
No |
.2537(14) Keep pool surface and pool floor free of debris. Observed debris on bottom of pool floor. CDI: cleaning during inspection. |
|
15
|
6
|
Premises: body hook and ring buoy with throw rope or lifeguard with rescue tube provided and properly located |
No |
No
|
No |
.2530(a) Provide ring buoy for rope 1.5 times the width of the pool or 50 ft whichever is less. Observed rope length > 36ft. CDI: cut to 36ft during inspection. |
|
17
|
4
|
Premises: decks unobstructed, properly drained, free of trip hazards |
No |
No
|
No |
.2522(a) Provide 6 ft of clear walking space around the pool at all times. Observed less than 6ft walking space around deck due to lawn chairs. CDI: lawn chairs moved back to provide 6ft clearance. |
|
25
|
2
|
Equipment room: equipment and chemicals kept in a dry, well-ventilated enclosure |
No |
No
|
No |
.2533(a) Pump room shall be weatherproof with a minimum ceiling height of 7 ft. Observed ceiling height less than 7ft. |