Submerged suction outlets meet ASME/ANSI A112.19.8-2007. Single drains protected. (.2537, .2539) GPM= ____Field verification complete=____ |
No |
No
|
No |
.2539(c) All pools, prior to permit issuance, shall provide documentation to the Department to verify suction outlet safety compliance. |
|
17
|
4
|
Premises: decks unobstructed, properly drained, free of trip hazards |
No |
No
|
No |
.2522(a) Provide 6 ft of clear walking space around the pool at all times.
Observed tables creating less than 6 ft clearance around deck. Tables moved.
.2537(2) Decks shall be kept free of trip hazards or offsets greater than 1/2" due to deterioration or changes from original deck profile. Observed hole in pool deck near diving board. CDI puddy used to fill hole. |
|
22
|
6
|
Premises: emergency telephone provided |
No |
No
|
No |
.2530(f) Provide signage with location of emergency phone if not visible from all areas inside pool enclosure.
Pool phone is not easily visible from pool deck. Phone location written on pool sign.
.2530(f) Signage with legible letters providing dialing instructions, address of pool and pool telephone number shall be posted at the emergency phone.
Observed no address written in pool box and number 911 has is not the same as listed on phone box. Had facility write address and phone number inside phone box. |
|
26
|
2
|
Equipment room: valves and pipes identified by color codes or labels |
No |
No
|
No |
.2518(d) Piping and valves shall be labeled with color codes or labels.
Observed some of the lines in the pump room not labeled. |