7
|
4
|
Pool maintenance: pool walls and floor kept clean, free of debris and in good repair |
No |
No
|
No |
Pool plaster in disrepair with significant damage noted in shallow end of pool. Pool must be replastered prior to issuance of operating permit in 2026. |
|
15
|
6
|
Premises: body hook and ring buoy with throw rope or lifeguard with rescue tube provided and properly located |
No |
No
|
No |
.2530(a) Provide ring buoy for rope 1.5 times the width of the pool or 50 ft whichever is less. - Observed rope for ring buoy to be longer than 1.5 times the width of the pool (42ft). - CDI - CPO corrected rope length to 42ft. |
|
24
|
4
|
Equipment room: approved pump, filter, and flow meter operating properly |
No |
No
|
No |
Per permit restrictions, flow meter must read 103GPM due to return line flow restriction. Observed flow meter reading 95GPM upon EHS arrival. - CDI - CPO cleaned filter and backwashed pool. Observed flow meter reading 103GPM after corrections. |
|
33
|
2
|
Dressing and sanitary facilities: hose bibbs and floor drains provided |
No |
No
|
No |
.2526(d) Provide hose bib so that all parts of restroom can be reached with a 50 ft hose. - No hose bib provided in or near restrooms. Provide hose bib. |