Pool maintenance: pool walls and floor kept clean, free of debris and in good repair |
No |
No
|
No |
.2537(14) Keep pool surface and pool floor free of debris. Observed slight debris present on bottom of floor. Clean as needed. |
|
15
|
6
|
Premises: body hook and ring buoy with throw rope or lifeguard with rescue tube provided and properly located |
No |
No
|
No |
.2530(a) Lifesaving equipment includes body hook and pole and USCG approved ring buoy with required rope length. Observed rope length too long. CDI - Cut to required length of 35’. |
|
24
|
4
|
Equipment room: approved pump, filter, and flow meter operating properly |
No |
No
|
No |
.2518(h) Provide approved pump in good repair. Observed pump on site as PENTAIR WHISPERFLO WF-8. Pump on PDSC form states the pump should be PENTAIR WHISPERFLO WFE-8. EHS spoke with K.Rudasill - Pump is provisionally approved due to it being on the same pump curve. ***** Trident has one week to provide an updated PDSC form or the permit will be suspended ***** |