Submerged suction outlets meet ASME/ANSI A112.19.8-2007. Single drains protected. (.2537, .2539) GPM= ____Field verification complete=____ |
No |
No
|
No |
Observed pump information on PDSC sheet not to match pump in equipment room. New pump is Hayward SP2615X20A. Provide corrected PDSC sheet to the Health Department. POOL CLOSED TO SWIMMING |
|
8
|
4
|
Pool maintenance: surface skimmers (with weirs, baskets and covers) or gutters clean, in good repair, and functioning properly, no floating debris |
No |
No
|
No |
Observed 2 weirs missing out of 4 total. Replace or Repair the weirs. |
|
12
|
4
|
Pool maintenance: inlets and other fittings in place and in good repair |
No |
No
|
No |
Observed some eyeball fittings missing. Observed Hydrostat to be missing its cover, creating an entrapment hazard. Correct this. |
|
15
|
6
|
Premises: body hook and ring buoy with throw rope or lifeguard with rescue tube provided and properly located |
No |
No
|
No |
Observed throw rope to be frayed and torn. When inspector pulled on rope to test the knot/strength, the rope fell apart. Replace the rope. Rope shall be exactly 32ft. long, measured from buoy. |
|
22
|
6
|
Premises: emergency telephone provided |
No |
No
|
No |
Observed call box to not have address and phone number. Correct this at call box. |