Submerged suction outlets meet ASME/ANSI A112.19.8-2007. Single drains protected. (.2537, .2539) GPM= ____Field verification complete=____ |
No |
No
|
No |
.2539(b) All suction outlets shall be protected by anti-entrapment cover/grates in compliance with APSP-7.
.2539(b) All suction fittings shall be installed in accordance with the manufacturer's instructions.
Observed uncovered vacuum suction line within pool at start of inspection. Observed one (1) return outlet with no fitting. CDI - CPO retrieved proper fittings from pool supply room during inspection. Eyeball fitting was installed for return outlet, and approved protective cover for vacuum line was screwed into place and secured (Pool constructed prior to May 1, 2010. |
|
11
|
2
|
Pool maintenance: diving equipment, ladders, steps and handrails properly placed, in good repair |
No |
No
|
No |
.2521(b) Ladders shall have slip-resistant tread. Observed ladder with no slip resistant tread.
.2521(b)(3)(A) Handrails, if removable, shall be installed in such a way than they cannot be removed without the use of tools. Observed one (1) loose handrail at steps of pool. CPO sealed loose handrail at deck using concrete at time of inspection. |
|
15
|
6
|
Premises: body hook and ring buoy with throw rope or lifeguard with rescue tube provided and properly located |
No |
No
|
No |
.2530(a) Provide ring buoy for rope 1.5 times the width of the pool or 50 ft whichever is less. Initially observed ring buoy rope at length of 33’. CDI - CPO cut rope length to permit specific length of 30’ |
|
22
|
6
|
Premises: emergency telephone provided |
No |
No
|
No |
.2530(f) Signage with legible letters providing dialing instructions, address of pool and pool telephone number shall be posted at the emergency phone. Observed emergency phone operable, but with improper telephone number on posted signage. CDI - Phone number was verified with emergency services during calls and improper phone number was covered using available tape by CPO; new phone number was written over it. |
|
24
|
4
|
Equipment room: approved pump, filter, and flow meter operating properly |
No |
No
|
No |
.2518(e) Provide a spare basket for pump. Observed no spare basket for pump. |