Premises Information

Return to Inspections
NameARBORETUM APARTMENTS
Address7700 ARBORETUM DRIVE
 
City/State/ZIP
CHARLOTTE NC 28226
Premise Type50 - Seasonal Swimming Pool
CountyMecklenburg
Inspection Date 6/16/2021
Final Score @ Grade
28
General Comments15 - Grab rope on ring buoy beginning to degrade. Operator contacted Leslie's pools during the inspection to replace. Provide photograph documentation of replaced USCG approved ring buoy by Friday, 6/18. 22 - Kings III phone does not provide option to talk through the phone. When number dialed, it "rings" the phone but button must be pushed to talk through. Address with Kings III so that 911 can contact the caller back directly through the phone. Given 30 days to correct. 30 - Could not verify check valve for fill line. Assure meets ASSE 1013 standards or rule .2512. Onsite visit to pool for in-field plan review. Items from previous visit verified as corrected. Observed digital flow meter F-1000 installed per mfg. instructions with at least 40" on inlet and 20" on outlet. Reading at 98 gpm. Permit Restriction: Flow meter must remain operable not to exceed 104 gpm due to limitation of return line. New pump Pentair Intelliflo VSF, 011056 approved set at 3450 rpm. E3912411 permit for pump change finaled. Open permit that is expired for rebar and new handrails from 2019 - E3348477. Per electrical inspector, Gerald Littles, bonding was verified when pump was finaled. Facility shall close out old permit by pulling a new electrical permit and attaching it to the old project. Did not appear to be an electrical hazard. Per Code Enforcement, bonding was verified for pool pump. Recommendations 1) No self-closure on door to indoor pump room. Recommend making door self-close, self-latch so that interior barrier does not account for outdoor pool barrier. 2) No back-up chlorinator installed on system. Only liquid. Recommend installing back-up chlorinator in case liquid automated system fails. Will Edwards present during the inspection. Permit issued for no night swimming. Your State permit will be available on our website at http://meckpools.charmeck.org. Your local permit sticker will be mailed.

Violations

 
CDI=Corrected During Inspection  R=Repeat Violation  VR=Verification Required 
Violation Item Demerits Violation Description CDIRVRComments
5 4 Water quality: daily written records of water quality and test kit kept on site No No No Some test kit reagents expired. Replace expired reagents. No logs maintained. Pool has not been open to public. Log book missing cyanuric acid and main drain check columns. Ensure chlorine, pH and main drain checks recorded daily. Cyanuric acid and total alkalinity recorded weekly.
8 4 Pool maintenance: surface skimmers (with weirs, baskets and covers) or gutters clean, in good repair, and functioning properly, no floating debris No No No Few skimmer weirs sticking. Keep operational.
11 2 Pool maintenance: diving equipment, ladders, steps and handrails properly placed, in good repair No No No Ladders and step handrails loose. Tighten and keep in good repair.
16 4 Premises: fence or barrier with self-closing, self-latching gates properly constructed and maintained No No No >4" between pickets in some areas. Maintain 4" or less between fence pickets. Picket fence and walled areas measuring less than 48". Maintain fence height at least 48" in height. Brick provides foothold in multiple areas around pool barrier. Eliminate footholds. Pool built pre-2010. No permit action required. Windows on to pool deck from package locker room could not be verified. Appears to have limiters. Ensure all windows on to pool deck do not open more than 4".
17 4 Premises: decks unobstructed, properly drained, free of trip hazards No No No >1/2" between deck drains located near fitness area entry. Repair prior to 2022 operating season. Not mentioned in previous reports. Maintain at 1/2" or less.
18 4 Premises: lifeguards present or warning signs posted No No No Warning signage not 4" lettering. Provide "Warning - No Lifeguard on Duty" in 4" lettering. Operator provided signage.
25 2 Equipment room: equipment and chemicals kept in a dry, well-ventilated enclosure No No No Ventilation in door but no cross ventilation in pump room. Original construction. Provide cross-ventilation or forced ventilation.
26 2 Equipment room: valves and pipes identified by color codes or labels No No No Labeling wearing off on piping in pump room. Relabel to clearly identify piping with color codes or labels.
27 2 Equipment room: filter backwash discharged through an air gap No No No No air gap at backwash line to pit. Provide air gap.