2
|
6
|
Water quality: disinfectant residual provided by |
No |
No
|
No |
0.1ppm free chlorine in the pool .2535(4) Maintain chlorine at least 1.0 ppm through NSF approved chlorinator. - Pre-permit item. |
|
8
|
4
|
Pool maintenance: surface skimmers (with weirs, baskets and covers) or gutters clean, in good repair, and functioning properly, no floating debris |
No |
No
|
No |
Skimmer equalizer lines not plugged in the skimmer. .2518(k) Skimmer equalizer lines shall be in compliance with ANSI/PHTA/ICC-7 or disabled. - Pre-permit item.
Missing one of two weirs. .2518(k) Provide functional weirs. - Pre-permit item. |
|
10
|
2
|
Pool maintenance: safety ropes with floats and contrasting color bands provided at shallow area breakpoints |
No |
No
|
No |
Breakpoint rope < 3/4” in diameter. .2523(e) Provide a minimum of 3/4 inch diameter safety rope at the breakpoint. - Pre-permit item. |
|
15
|
6
|
Premises: body hook and ring buoy with throw rope or lifeguard with rescue tube provided and properly located |
No |
No
|
No |
Body hook with only one screw attaching it to the pole. .2530(a) Provide at least 12 ft. long pole with body hook securely attached. - Pre-permit item. |
|
16
|
4
|
Premises: fence or barrier with self-closing, self-latching gates properly constructed and maintained |
No |
No
|
No |
Service gates missing self-latching mechanism. .2528(a) All gates other than pedestrian access gates shall have a self-latching device. - Will follow up with facility.
Gate at bathrooms does not meet requirements. Door to bathrooms not self-closing. .2537(b) All gates and doors shall be self-closing, self-latching. - Will follow up with facility.
Gates with gaps > 2” under gate. .2528(a) Maintain 2" or less under gates. - Will follow up with facility.
Main gate with decorative cutouts and footholds. .2528(a) Where barrier consists of both horizontals and vertical members and horizontals are less than 45" apart, the horizontal member shall be located on the inside of the barrier with openings between vertical members no greater than 1.75 inches. - Will follow up with facility. |
|
24
|
4
|
Equipment room: approved pump, filter, and flow meter operating properly |
No |
No
|
No |
Flow meter stuck. .2518(g) Keep the flow meter operational. - Pre-permit item. |
|
27
|
2
|
Equipment room: filter backwash discharged through an air gap |
No |
No
|
No |
Backwash plumbed directly into pump room floor. .2513(b) Filter backwash shall be discharged through an air gap. |