7
|
4
|
Pool maintenance: pool walls and floor kept clean, free of debris and in good repair |
No |
No
|
No |
Some rust staining around lights in pool. Ensure stainless steel used in light fixtures. Brush/eliminate staining from pool wall to ensure 50% light reflectance is met. |
|
16
|
4
|
Premises: fence or barrier with self-closing, self-latching gates properly constructed and maintained |
No |
No
|
No |
New barrier installed. Additional barrier replaced in between site visits. New barrier with <45" from smaller panel to larger panel horizontals. Facility added permanent "temporary" cover over lower horizontal until fence company can replace mesh on full fence. Pictures provided. |
|
23
|
4
|
Equipment room: chlorine or bromine automatic feeders that meet NSF Standard 50 |
No |
No
|
No |
No flow meter on chlorinator. Provide flow meter per NSF approval. Existing chlorinator. If ever replaced, provide flow meter per NSF requirement. |
|
24
|
4
|
Equipment room: approved pump, filter, and flow meter operating properly |
No |
No
|
No |
Small leak at pump. Continue to monitor and repair as needed.
Backwash line does not direct water into pit. Angled to left of floor drain. Recommend moving backwash line to go directly above pit so not to get the floor in the pump room wet. |
|
25
|
2
|
Equipment room: equipment and chemicals kept in a dry, well-ventilated enclosure |
No |
No
|
No |
Drain missing cover in middle of pump room. Provide cover for floor drain in pump room to eliminate hazard. |
|
30
|
2
|
Dressing and sanitary facilities: approved water source, no cross connections |
No |
No
|
No |
Hose bib in pump room without backflow prevention device. Provide backflow prevention device. |
|
33
|
2
|
Dressing and sanitary facilities: hose bibbs and floor drains provided |
No |
No
|
No |
No hose bib or floor drain in restrooms. Pool built in 1976. Original construction. Provide hose bib and floor bib. |