| CDI=Corrected During Inspection | |
R=Repeat Violation | |
VR=Verification Required | |
|
|
| Violation Item
| Demerits
| Violation Description
| CDI | R | VR |
|
|
1
|
0
|
Floors and carpets cleanable, clean, good repair; carpet odor free |
No |
No
|
No |
1309 (a) and (b) The floors in an institution shall be made of smooth, non-absorbent materials and shall be kept clean and in good repair. When carpet is present, it must be kept clean, odor free, and in good repair.- Observed flooring in supplies closet in ACU need cleaning and tightly up. |
|
2
|
0
|
Walls and ceilings clean, good repair |
No |
No
|
No |
.1310 (a) The interior walls of the institution, including doors, windows and window trim, and ceilings, shall be kept clean and in good repair. Observe stained ceiling tiles in 3074 storage. Check for leaks and repair. |
|
7
|
2
|
Facilities provided, accessible, clean, good repair |
No |
No
|
No |
REPEAT
.1312 (a) All institutions shall provide toilet, handwashing, and bathing facilities that are available for use by residents and staff. These facilities shall be kept clean and in good repair. Observed pink residue around shower drain and shower head in 301. Observed part of shower bench loose in 3277. Observed bolt out of shower chair and shower head dripping in 3279. Observed hand sink was blocked by trash can and a big roller bag at the hand sink in the lab. CDI- Items removed at the time of inspection. Ensure to not block any hand washing sink at anytime. |
|
16
|
0
|
Hot water between 105°F and 116°F |
No |
No
|
No |
.1313 (d) Institutions shall provide water heating facilities. Hot and cold running water under pressure shall be provided to carry out all operations. Hot water shall be provided at temperatures between 105 degrees Fahrenheit and 116 degrees Fahrenheit at handwashing and bathing facilities.- Observed hot water temperature measured about 101F- 103F (Radiology, ER, MSU2). Observed hot water at 103 in 3247. Observed hot water at 100 in 3251. Needs to be 105-116F. |
|
38
|
0.50
|
Food service equipment and utensils clean, good repair |
No |
No
|
No |
.1320 (a) All food service equipment and utensils shall be kept clean and in good repair.- Observed microwaves in nourishment room need detail cleaning and keep clean. Observed build up in refrigerators in Nourishment rooms 3306 and 3374. |
|
45
|
0
|
Hot and cold holding equipment provided; thermometers provided, accurate |
No |
No
|
No |
.1323 (b) Hot and cold holding equipment shall be used to maintain the required temperatures for TCS food. Each refrigeration unit shall be provided with an indicating thermometer that is accurate to ±3 degrees Fahrenheit or ±1.5 degrees Celsius. Observed refrigerator thermometers not working correctly in 3073. |
|