2
|
0
|
Walls and ceilings clean, good repair |
No |
No
|
No |
.1310 (a) The interior walls of the institution, including doors, windows and window trim, and ceilings, shall be kept clean and in good repair. Observed scuffed and peeling walls throughout 4 North. Repair. REPEAT *Points not escalated due to majority of walls throughout hospital in good repair. |
|
7
|
1
|
Facilities provided, accessible, clean, good repair |
No |
No
|
No |
.1312 (a) All institutions shall provide toilet, handwashing, and bathing facilities that are available for use by residents and staff. These facilities shall be kept clean and in good repair. Observed blocked hand sink in soiled utility room. Observed hot water hand sink knob not working in room 5 in ICU. Repair. REPEAT |
|
16
|
0
|
Hot water between 105°F and 116°F |
No |
No
|
No |
.1313 (d) Institutions shall provide water heating facilities. Hot and cold running water under pressure shall be provided to carry out all operations. Hot water shall be provided at temperatures between 105 degrees Fahrenheit and 116 degrees Fahrenheit at handwashing and bathing facilities. Observed hot water in ED room 4 reach 79F. Ensure hot water is between 105-116F. |