13
|
1
|
Lavatory and bathing hot water between 100 and 116 F |
No |
No
|
No |
Maintain the hot water at all resident accessible handwashing sinks and bathing facilities within the temperature range of 100°F to 116°F. 15A NCAC 18A .1312 (e). Observed water temperatures above 116F in ACU, Pre Op, PACU, and first floor A. Water temperatures were corrected during the inspection. |