2
|
0
|
Walls and ceilings clean, good repair |
No |
No
|
No |
.1310 (a) The interior walls of the institution, including doors, windows and window trim, and ceilings, shall be kept clean and in good repair. Observed walls peeling outside of quiet room 2 on ED side. Repair. |
|
16
|
1.50
|
Hot water between 105°F and 116°F |
No |
No
|
No |
.1313 (d) Institutions shall provide water heating facilities. Hot and cold running water under pressure shall be provided to carry out all operations. Hot water shall be provided at temperatures between 105 degrees Fahrenheit and 116 degrees Fahrenheit at handwashing and bathing facilities. Observed hot water reach 119F in hall restroom on inpatient north side. Observed hot water at 74F in hall bathroom on ED side. Adjust water temperature so that hot water is between 105-116F. REPEAT |