5
|
2
|
Ambient air temperature 65 to 85 F, equipment clean |
No |
No
|
No |
Observed dust build up on vent covers throughout inspection. Needs to be cleaned. REPEAT.
**Keep all ventilation equipment clean and in good repair. 15A NCAC 18A .1311 (b). |
|
13
|
1
|
Lavatory and bathing hot water between 100 and 116 F |
No |
No
|
No |
Observed water temperatures fluctuation during inspection, ranging from 57F in 2E-83 to 122F in patient bathroom on 1 North. Temperatures needs to be adjusted.
**Maintain the hot water at all resident accessible handwashing sinks and bathing facilities within the temperature range of 100°F to 116°F. 15A NCAC 18A .1312 (e). |