2
|
0
|
Walls and ceilings clean, good repair |
No |
No
|
No |
.1310 (a) The interior walls of the institution, including doors, windows and window trim, and ceilings, shall be kept clean and in good repair.
Observed water stained ceiling tile in Plebotomy and black microbial growth in the restroom in radiology. Observed staining wall, need new paint in room 3 and 4 on 10th floor. |
|
10
|
0
|
Handwashing facilities properly located and equipped |
No |
No
|
No |
.1312 (d) Hand washing facilities shall be equipped with running water and a tempering device. Observed no disposable towels at handsink in soiled utility room and in nourishment area in Dickson Heart Unit. Observed no soap and paper towels available in soiled utility 8th floor, no soap in staff restroom 9th floor, no paper towel in soiled utility 10th floor, no paper towel on 9th floor nourishment area. Ensure to provide all hand washing supplies at all hand sink at all times. |
|
16
|
1.50
|
Hot water between 105°F and 116°F |
No |
No
|
No |
.1313 (d) Institutions shall provide water heating facilities. Hot and cold running water under pressure shall be provided to carry out all operations. Hot water shall be provided at temperatures between 105 degrees Fahrenheit and 116 degrees Fahrenheit at handwashing and bathing facilities.
Observed hot water at 119F at nourishment area handsink in unit CURU. Observed hot water 84F in Adult ED major treatment room 13. Observed no water available in patient room #8619.
- Observed in children hospital no hot water at hand sink in soiled utility room 9th floor and 8th floor laundry room. Observed hot water measured between 79F -104F on 7th floor playroom, NPCN, 6th floor, 9th floor PICU, 8th floor playroom and nourishment room. Ensure to provide tempered water between 105F to 116 F at anytime.
Repeat. |
|
38
|
0.50
|
Food service equipment and utensils clean, good repair |
No |
No
|
No |
.1320 (a) All food service equipment and utensils shall be kept clean and in good repair. Observed microwave in nourishment area in 5 tower and 11T with build up on ceiling. Observed spill on door in refrigerator in 10DE. Observed soiled/stained microwave/refrigerator in nourishment area on 10th, 11th family snack room. |