2
|
1
|
Walls and ceilings clean, good repair |
No |
No
|
No |
.1310 (a) The interior walls of the institution, including doors, windows and window trim, and ceilings, shall be kept clean and in good repair. Observed water stained ceiling tile at soiled utility room in Adult ED. Touch up paint and repairs needed near EVS storage room on CMC side. Observed wall edging broken in 10918. Observed wall paper peeling in hall of 9B. Observed wall damage next to hopper in soiled utility in 10B. Observed scuffed walls or doorframes in various areas in LCH and 6A, 6B, 6T, 9th (room 10), 10th (room 10), and 11th floors. Observed water stained ceiling tiles in ultrasound clean utility. |
|
10
|
0
|
Handwashing facilities properly located and equipped |
No |
No
|
No |
.1312 (d) Handwashing facilities shall be supplied with soap and disposable towels or hand-drying devices. Observed hand sink stocked with sanitizer not soap in nourishment room 8T. |
|
16
|
1.50
|
Hot water between 105°F and 116°F |
No |
No
|
No |
.1313 (d) Institutions shall provide water heating facilities. Hot and cold running water under pressure shall be provided to carry out all operations. Hot water shall be provided at temperatures between 105 degrees Fahrenheit and 116 degrees Fahrenheit at handwashing and bathing facilities. Observed hot water 79F in 3T and 89F in 3T. Observed 74F in 6220. Observed hot water 81-91F on 6th floor CVICU. Repeat. No escalation in points due to improvement. |
|
32
|
0
|
Furnishings clean and in good repair; mattresses dry, clean, good repair |
No |
No
|
No |
.1319 (a) Furnishings in an institution, including furniture, curtains, rugs, and blinds, shall be kept clean and in good repair. Mattresses shall be kept clean, dry, and in good repair. Observed laminate cushion seats peeling in rooms 6017A and 8002. |