Select your filters and click the Search button to search for data, or click Clear to clear all filters
 
Logo Main Menu
Mecklenburg County Health Dept
Public Health Inspections
Select your filters and click the Search button to search for data, or click Clear to clear all filters
 
  
 

Premises Information

Return to Inspections
NameVIA HEALTH PARTNERS
Address11900 VANSTORY DRIVE
 
City/State/ZIP
HUNTERSVILLE NC 28078
Premise Type40 - Rest/Nursing Homes
CountyMecklenburg
Inspection Date 10/20/2025
Final Score @ Grade
97.50
General Comments

Violations

 
CDI=Corrected During Inspection  R=Repeat Violation  VR=Verification Required 
Violation Item Demerits Violation Description CDIRVRComments
16 1.50 Hot water between 105°F and 116°F No No No REPEAT .1313 (d) Institutions shall provide water heating facilities. Hot and cold running water under pressure shall be provided to carry out all operations. Hot water shall be provided at temperatures between 105 degrees Fahrenheit and 116 degrees Fahrenheit at handwashing and bathing facilities. - Observed hot water temperature throughout the facility measured between 120F- 122F. Provide tempered water temperature between 105F-116F.
17 1 Back-up water supply plan available and complete No No No REPEAT .1313 (e) The institution shall have a written plan to obtain a backup water supply in the event that the institution's primary water supply is interrupted for more than four consecutive hours. The written plan shall identify a backup water supply or alternate source of water that provides two liters of potable water per day per resident and institution employee for drinking and potable water for food preparation, hand washing, bathing, cleaning, dishwashing, laundry, and disposal of bodily waste. This may include a plan for relocating residents to a facility with a water supply that satisfies Paragraph (a) of this Rule. If an institution's primary water supply or backup water supply becomes unsafe for human consumption, then the water sources within the institution, such as sink faucets, shall be labeled or hooded to prevent their use, and the administrator shall provide potable water for use by the institution's residents and employees.- Observed water back up supply plan available upon request, per previous inspection reports, the facility still needs to revise the plan and use correct terminology for intent of purpose (Portable water vs. non portable water). Revision of correct terminology needed. Have a complete corrected plan available.
32 0 Furnishings clean and in good repair; mattresses dry, clean, good repair No No No General Comment: .1319 (a) Furnishings in an institution, including furniture, curtains, rugs, and blinds, shall be kept clean and in good repair. Mattresses shall be kept clean, dry, and in good repair.- Observed damaged, torn, and frayed furniture in almost all the rooms. Repair/replace of the furniture.