Walls and ceilings clean, good repair |
No |
No
|
No |
Observed water stained ceiling tile in the laundry room on the 2nd floor. Only stained ceiling tile observed during the inspection.
**.1310 (a) The interior walls of the institution, including doors, windows and window trim, and ceilings, shall be kept clean and in good repair. |
|
5
|
0
|
Ventilation equipment clean, good repair |
No |
No
|
No |
Observed vent cover with minor build up in the storage closet. Cleaned during the inspection.
**.1311 (b) Ventilation equipment shall be kept clean and in good repair. |
|
7
|
1
|
Facilities provided, accessible, clean, good repair |
No |
No
|
No |
Observed rusted toilet chair in rooms C218 and C222. Needs to be replaced.
**.1312 (a) All institutions shall provide toilet, handwashing, and bathing facilities that are available for use by residents and staff. These facilities shall be kept clean and in good repair. |
|
16
|
1.50
|
Hot water between 105°F and 116°F |
No |
No
|
No |
Observed hot water range from 121-130F during the inspection.
**.1313 (d) Institutions shall provide water heating facilities. Hot and cold running water under pressure shall be provided to carry out all operations. Hot water shall be provided at temperatures between 105 degrees Fahrenheit and 116 degrees Fahrenheit at handwashing and bathing facilities. |