Walls and ceilings clean, good repair |
No |
No
|
No |
.1310 (a) The interior walls of the institution, including doors, windows and window trim, and ceilings, shall be kept clean and in good repair. Observed peeling wall around vent in men’s staff bathroom. Repair. |
|
5
|
0.50
|
Ventilation equipment clean, good repair |
No |
No
|
No |
.1311 (b) Ventilation equipment shall be kept clean and in good repair. Observed multiple a/c filters with dust buildup in resident rooms. Keep clean. |
|
16
|
3
|
Hot water between 105°F and 116°F |
No |
No
|
No |
.1313 (d) Institutions shall provide water heating facilities. Hot and cold running water under pressure shall be provided to carry out all operations. Hot water shall be provided at temperatures between 105 degrees Fahrenheit and 116 degrees Fahrenheit at handwashing and bathing facilities. Observed hot water between 125-128F at all hand sinks inspected throughout facility. Ensure hot water is between 105-116F. REPEAT |
|
28
|
0.50
|
No pest presence; effective pest control measures |
No |
No
|
No |
.1317 (a) Pests shall not be present in an institution's building or buildings. Observed several small flies in bathroom of room number 2. No pests should be present in the facility. |