1
|
0.50
|
Ventalation clean and in good repair |
No |
No
|
No |
Observed multiple of the AC unit vents collecting dust.Ventilation located in Lobby, Halls, Stairs, and Vending Areas, shall be kept clean and in good repair. 15A NCAC 18A .1808 (b). |
|
13
|
1.50
|
Hot and cold running water provided (116-128 F) in guestrooms |
No |
No
|
No |
Observed the water on the 5th & 4th floors at 132F, the 3rd floor at 133F, the 2nd floor at 138F, and the1st floor at 136F.Hot water in guest rooms shall be provided at a temperature of no less than 116°F (46.7°C) and no more than 128°F (53.3°C). 15A NCAC 18A .1810 (e). |
|
17
|
3
|
Ice machines clean and in good repair; ice machine meet requirements |
No |
No
|
No |
Repeat Non-Compliance: Observed black buildup in the chutes in all of the ice machines in the building.Ice Machines, equipment, utensils, and the room or area in which the machines are located shall be kept clean and in good repair. 15A NCAC 18A .1811 (c). |