Ventalation clean and in good repair |
No |
No
|
No |
Observed: Ventilation near the vending machines collecting dust and rust on N Tower throughout.Ventilation located in Lobby, Halls, Stairs, and Vending Areas, shall be kept clean and in good repair. 15A NCAC 18A .1808 (b). |
|
3
|
0.50
|
Floors, walls and ceilings clean and in good repair |
No |
No
|
No |
Observed: Minor floor, wall, and ceiling damage throughout housekeeping closets in N Tower. Water damaged ceiling tiles and missing ceiling tiles in the basement. Water damaged ceiling tiles in the 14floor hall in S Tower. Water damage to the ceiling in the vending areas of N Tower (floors 11, 9). Ceiling drywall damage in the hall near room 270 in N Tower.Floors, walls, and ceilings located in Lobby, Halls, Stairs, and Vending Areas, shall be kept clean and in good repair. 15A NCAC 18A .1808 (b). |
|
13
|
1.50
|
Hot and cold running water provided (116-128 F) in guestrooms |
No |
No
|
No |
Observed: Hot water at 110-114F on N Tower upper floors and 140F in N Tower lower floors.Hot water in guest rooms shall be provided at a temperature of no less than 116°F (46.7°C) and no more than 128°F (53.3°C). 15A NCAC 18A .1810 (e). |
|
30
|
1.50
|
Storage provided for supplies, linen and equipment; kept clean |
No |
No
|
No |
Observed: Guest related items (pillows, water, drinking cups, etc) stored on the housekeeping closet floors throughout.Cabinets, shelves, and storage rooms shall be constructed to facilitate cleaning and kept clean. 15A NCAC 18A .1813 (b). |